Power Line Safety….always look UP!!!

Here is an article I wrote a few years back (circa 2007/2008)…It still holds true today


“I just saw this one on the news, and had to write a bit for you guys to pass on to the ham community, especially the newer hams. Please forward this in its entirety, as I am using my professional back ground to back up my statements.

><><><><><><><><><><><><><><>

We lost another ham today, and it is a very sad event. The parties involved, were installing a Comet FIBERGLASS antenna, that came in contact with a single 7620V power line. Now how do I know what the exact voltage is? I built and maintained the substation that fed this circuit. I spent 27 years as a substation technician for the Board of Public Utilities. I am still in this field. So, I feel I have some experience in what I am passing along.

In a nutshell, the location of the accident was a few blocks from the substation. The wires you see going thru the residential areas are AT MINIMUM 7200 volts from each wire to ground, and between any two of them is 13,800 volts. This is nothing to play with at any time. I have seen a fault TOTALLY vaporize 1″ copper buss (which is solid). Imagine what it can do to a human. Each wire is fed from what is called a 3 phase line. From there, it can be broken off and sent down a property line as a single wire. Those are called “laterals” Yes, you will see a device at the break out point, and this is a fuse. BUT the caution needs to be conveyed. These fuses are in the 60-100 amp range. This is at 7200 volts.  
On top of that, anytime a tree falls across a line, or a pole gets hit, there is a circuit on the “feeder” at the substation that AUTOMATICALLY closes the feeder back in, and TRIES to restore the power to the area. Some of these “reclosers” can operate 2-5 times, depending on how they are set.
Now from the substation end, the protective device is set for the full fault capabilities of the line. In the case of BPU, this can be set at 600 AMPS, and multiples of that value. The protective devices are set for what is called a “time” or and “instantaneous” operation. Picture a slow blow fuse and a fast blow, and you will understand the difference in the settings. These setting are at multiples of the 600 amp value. So, if there is a direct short, then it will not trip until it reaches a value at, oh lets say, 8 times that value. This value is so the Lateral fuse can do its job. So we are looking at 4800 amps. and this is at 7200 volts and lower. 
So, it trips, then it energizes it AGAIN. The possibility of survival if you are tied up in the wiring is slim and none.

Now remember how I said they were installing a FIBERGLASS antenna?
Well guess what. It is metal inside. Yes, fiberglass does not radiate as we all know. Hence the metal. That is what caused the accident. They got too close to the line (remember your ‘magnetic lines of flux’ theory? If not, look it up on the web).
There is a minimum approach area that MUST be followed. This changes for ALL voltages. This distance must NOT be broken. If it is….. a flashover will happen, and it is not pretty.
Electricity will find the shortest path to ground. In this case it was a couple of men.


Folks, this is nothing to take chances with. In my almost 30 yrs as a ham, and 27 yrs in the power utility field, I have seen way too many “accidents.” Stop, look and if it is close or SEEMS that way- DON’T.

Find another place. High voltage lines are NOT forgiving. Your life depends on it. You always hear “it is the amps not the volts”, well I can tell you when you get at these levels, who is going to argue what killed the person who had the accident. PLEASE ,PLEASE follow the warnings. ANYWHERE close is too close. Stay safe, and I hope we can enjoy many more years of hamming.

Thanks Guys,

Chuck Kraly, K0XM”